ArcAngel is better for the job than solid-copper conductors in five distinct ways: mechanically, thermally, electrically, financially, and risk of theft.
ArcAngel was designed to replace common sizes of copper used in grounding applications with a more flexible version of traditional CCS. The resulting high-strand-count conductor sizes are named for the current they can carry, per IEEE Standard 80-2013 Table 6. For example, ArcAngel 44 can carry 44,000 Amps for 500 ms.
As added advantage of the higher strand count, ArcAngel provides greater mechanical strength. 2/0-sized ArcAngel has higher breakload than a common 4/0 copper conductor, which provides substation design engineers new options to explore in software modeling tools, like CDEGS v18, for optimizing the cost of a substation ground grid.
101 kA
97 kA
26,898 lbf
15,240 lbf
Excellent
Good
61
19
Indicator, Bare
—
73 kA
68 kA
18,785 lbf
10,680 lbf
Excellent
Good
61
19
Indicator, Bare
—
52 kA
48 kA
13,411 lbf
7,627 lbf
Excellent
Good
61
19
Indicator, Bare
—
44 kA
41 kA
11,455 lbf
5,983 lbf
Excellent
Good
61
19
Indicator, Bare
—
28 kA
26 kA
7,167 lbf
3,760 lbf
Excellent
Good
19
19
Indicator, Bare
—
14 kA
13 kA
3,619 lbf
1,928 lbf
Excellent
Good
19
1
Indicator, Bare
—